VA-6100MA Voice Alarm Controller

The Details Related Solution Related Cases Related Video Download


Descriptions:


VA-6100MA is a core management and control device for public address broadcasting and emergency voice alarm broadcasting. It can be directly controlled and system status checked on a 5-inch HD touch screen. It support user-defined function and system control through PC management software, automatic monitoring and management to physical partition status and terminal equipment, automatic completing  the monitoring and management of terminal equipment, aautomatic executing the pre-programming control, etc.


Features:


* 5 inch HD color touch graphical man-machine operation interface.

* One button for emergency alarm.

* Support zone selection, zone distribution, grouping operation, with independent zone volume adjustment.

* Support user-defined zone name, group name, host name, easy to operate and manage.

* Support event trigger, timing trigger control output.

* Support zone monitor, equipment status real-time indication.

* Support event trigger phone call notification, can be set re-calling times when no answering.

* Support Ethernet online configuration, control interface work offline.


Specifications:


Electrical indicators

 

AC power supply

Voltage

AC110-240V  50-60Hz

Maximum current

0.5A

Fuse

250V/1A, slow

Power consumption

36W

DC power supply

Voltage

DC24V, 18-31V adaptive

Maximum current

1.5 A

Performance Index

 

Emergency microphone

Sensitivity

10mV

Impedance

600Ω

Line input

Input channel

5 channels (1 channel Caron interface, 4 channels RCA interface)

Sensitivity

385mV (balanced), 775mV (unbalanced)

Impedance

20KΩ10KΩ

Recording output

Distortion

0.1%

Amplitude

200mV

Frequency response

200-16KHz

SNR

68dB

Contact output

System fault relay output

Short circuit, no voltage

Fire linkage relay output

Short circuit, no voltage

8 relay programmable outputs

Short circuit, no voltage

Programmable DC24V power output

DC24V, 0.3A

Contact input

Trigger type

Short-circuit input, short-circuit input with detection, and voltage input

Short circuit mode

3.3V voltage, short-contact trigger, no linkage line monitoring function

Short mode with detection

3.3V voltage, short-contact trigger, support linkage line fault alarm

Voltage mode

18-31V voltage input, voltage trigger, support linkage line fault alarm

Fire reset input

Contact ≥ 0. 5S, no voltage

Voice message

Data Format

MP3 or WMA format

Storage type

TF card

Amount of information

65535 (maximum programmable 1000)

Retention time

> 10 years

Other Information

Data Format

HEXBIN

Storage type

Nand Flash

Amount of information

100,000

Retention time

> 10 years